Date:05-09-2024STATE OF CALIFORNIA 
LAST AND NEXT SAMPLE REPORT
SYSTEM NO.:0800555SYSTEM NAME:GASQUET C.S.D.COUNTY:DEL NORTE 
SOURCE NO.:All SourcesSOURCE NAME:N/ASOURCE CLASS:N/ASTATUS:N/A



Click to hide / show columns: PS Codes | Group Name | Analyte Number | Analyte Name | Detected Level |Less Than | RL | Unit | MCL | DLR | Last Sampled | Frequency | Next Due | Notes

PS Codes Group Name Analyte Number Analyte Name Results Unit MCL DLR Last Sampled Frequency Next Due Notes
Detected Level Less Than RL
CA0800555_001_001 SECONDARY/GP-203210 1928 ALKALINITY, BICARBONATE 65.000 1.000 MG/L 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1919 CALCIUM 2.400 0.100 MG/L 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1929 ALKALINITY, CARBONATE < 1.000 MG/L 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1017 CHLORIDE 3.900 0.500 MG/L 500 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1905 COLOR 18.000 3.000 UNITS 15 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1022 COPPER, FREE < 5.000 UG/L 1000 50 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 2905 FOAMING AGENTS (SURFACTANTS) < 0.050 MG/L .5 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1915 HARDNESS, TOTAL (AS CACO3) 64.000 1.000 MG/L 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1021 HYDROXIDE AS CALCIUM CARBONATE < 1.000 MG/L 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1028 IRON < 50.000 UG/L 300 100 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1031 MAGNESIUM 14.000 0.100 MG/L 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1032 MANGANESE 1.700 1.000 UG/L 50 20 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1920 ODOR 3.000 1.000 TON 3 1 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1925 PH 7.600 pH 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1050 SILVER < 10.000 UG/L 100 10 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1052 SODIUM 2.500 0.100 MG/L 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1064 CONDUCTIVITY @ 25 C UMHOS/CM 140.000 1.000 UMHO/CM 1600 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1055 SULFATE 1.500 1.000 MG/L 500 .5 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1930 TDS 86.000 10.000 MG/L 1000 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 0100 TURBIDITY 0.690 0.100 NTU 5 .1 10-12-2023 108 2032/10
CA0800555_001_001 SECONDARY/GP-203210 1095 ZINC 5.200 5.000 UG/L 5000 50 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-202308 1002 ALUMINUM < 50.000 UG/L 1000 50 08-26-2014 108 2023/08 DUE NOW
CA0800555_001_001 INORGANIC-203210 1074 ANTIMONY, TOTAL < 5.000 UG/L 6 6 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-203210 1005 ARSENIC < 2.000 UG/L 10 2 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-203210 1010 BARIUM 5.100 5.000 UG/L 1000 100 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-203210 1075 BERYLLIUM, TOTAL < 1.000 UG/L 4 1 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-203210 1015 CADMIUM < 1.000 UG/L 5 1 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-203210 1020 CHROMIUM < 5.000 UG/L 50 10 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-203210 1025 FLUORIDE < 0.100 MG/L 2 .1 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-203210 1035 MERCURY < 1.000 UG/L 2 1 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-203210 1036 NICKEL 13.000 5.000 UG/L 100 10 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-202610 1039 PERCHLORATE < 2.000 UG/L 6 2 10-12-2023 36 2026/10
CA0800555_001_001 INORGANIC-203210 1045 SELENIUM < 5.000 UG/L 50 5 10-12-2023 108 2032/10
CA0800555_001_001 INORGANIC-203210 1085 THALLIUM, TOTAL < 1.000 UG/L 2 1 10-12-2023 108 2032/10
CA0800555_001_001 NITRATE/NITRITE-202410 1040 NITRATE < 0.100 MG/L 10 .4 10-12-2023 12 2024/10
CA0800555_001_001 NITRATE/NITRITE-202610 1041 NITRITE < 0.100 MG/L 1 .4 10-12-2023 36 2026/10
CA0800555_001_001 RADIOLOGICAL-203210 4109 GROSS ALPHA PARTICLE ACTIVITY < 1.000 PCI/L 15 3 10-12-2023 108 2032/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2943 BROMODICHLOROMETHANE 7.500 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2942 BROMOFORM < 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2941 CHLOROFORM 33.000 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2454 DIBROMOACETIC ACID < 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2944 DIBROMOCHLOROMETHANE 1.200 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2451 DICHLOROACETIC ACID 11.000 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2456 TOTAL HALOACETIC ACIDS (HAA5) 25.000 6.000 UG/L 60 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2453 MONOBROMOACETIC ACID < 1.000 UG/L 1 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2450 MONOCHLOROACETIC ACID < 2.000 UG/L 2 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2950 TTHM 41.000 4.000 UG/L 80 10-12-2023 12 2024/10
CA0800555_DST_901 DISINFECTION BYPRODUCTS-202410 2452 TRICHLOROACETIC ACID 14.000 1.000 UG/L 1 10-12-2023 12 2024/10
PS Codes Group Name Analyte Number Analyte Name Detected Level Less Than RL Unit MCL DLR Last Sampled Frequency Next Due Notes

RL – Reporting Level means the level to which the laboratory reported the presence of an analyte. For radionuclides, Reporting Level is the MDA95.

DLR – Detection Limit for purposes of Reporting (DLR) means the designated minimum level at or above which any analytical finding of a contaminant in drinking water resulting from monitoring required under Chapter 15 of Title 22 shall be reported to the State Board (California Code of Regulations Section § 64400.34)

For addtional definitions, please refer to our data dictionary.